Factory direct — 40–60% below Megger / BAUR list pricing · Worldwide shipping · Request a quote
TriEdge TechnologiesTriEdge Technologies Get a Quote

Reading TDR Waveforms: How to Tell a Joint from a Fault

The TDR screen shows a waveform. To the experienced eye, it's a story of the cable's entire life — every splice, every repair, every weakness. To the untrained eye, it's a confusing line with bumps on it.

The difference between the two is the difference between a 2-hour repair and a 2-day search. This guide teaches you how to read the trace.

1. The Anatomy of a TDR Trace

Trace element What it means
Launch pulse The initial pulse at the connection end (distance 0)
Far-end reflection The end of the cable — a large reflection at full length
Impedance-change reflections Smaller bumps at every joint, splice, and change in cable construction
Fault reflections Strong reflections at unexpected positions
Baseline drift Gradual changes along the trace — can indicate moisture or degradation

2. Polarity Tells You the Fault Type

The direction of the reflection tells you whether the impedance went up or down:

  • Positive (upward) reflection — impedance increased: open circuit, broken conductor, or a cable with higher impedance
  • Negative (downward) reflection — impedance decreased: short circuit, low-resistance fault, or a splice with lower impedance

This is why the same trace can instantly tell a veteran "open at 780 m" from "short at 780 m."

3. Joint vs Fault — The Three-Question Test

When you see a reflection, don't guess. Ask:

1. Is it at a documented position? If the reflection sits exactly at a known joint coordinate from the as-built records, it's almost certainly that joint. Joints are your friend — they help you calibrate distance.

2. How strong is it? A healthy joint produces a small reflection — a few percent of the launch pulse. A fault produces a strong reflection, often 50-100% of the pulse. If a reflection is disproportionately large, suspect a degraded joint or fault at that point.

3. Was it there before? This is the decisive question. If you have a commissioning baseline trace, compare: any NEW reflection that wasn't in the baseline is a fault or developing defect — even if it's small.

4. The Baseline Method (Professional Standard)

The professional workflow is not about interpreting a single trace in isolation — it's about comparison:

  1. At commissioning, save a baseline trace for every phase with its velocity factor recorded
  2. On every fault job, shoot the same trace and overlay it against the baseline
  3. Identify new reflections — these are the suspects
  4. Correlate with records — distance to the new reflection + route chart = dig point

This is why A10 series TDRs include waveform storage as a core feature: a TDR without trace comparison is a flashlight without a map.

5. Common Mistakes to Avoid

  • Trusting a single trace — always shoot multiple times and compare
  • Ignoring the velocity factor — a 5% VF error shifts every distance (see our velocity factor guide)
  • Mistaking a large joint reflection for a fault — a degraded joint can look like a fault; check joint records first
  • Forgetting to save the trace — the next engineer (or you, in three years) will need it

6. When the Trace Looks Clean

If the cable is dead but the TDR shows nothing, you're probably facing a high-resistance fault — above a few hundred ohms, it reflects too little energy to see. The solution is conditioning: burn down or bridge-measure the fault into a locatable state (see our high-resistance fault guide).

How TriEdge Helps

The A10 and A10 Advanced TDRs make trace comparison practical:

  • 0–100 km range, ±0.5 m accuracy
  • Waveform storage and comparison — overlay today's trace on the commissioning baseline
  • Velocity factor presets + fine manual calibration
  • Linux-based operating system for stable field operation

Factory-direct pricing, 40–60% below equivalent Western brands.

View A10 → · Full catalog (PDF)


FAQ

How can I tell if a reflection is a joint or a fault? Check three things: (1) is it at a documented joint position? (2) how strong is the reflection? (3) was it present in the commissioning baseline? A strong reflection at an unexpected position that wasn't in the baseline is a fault.

What does a positive reflection mean on a TDR? A positive (upward) reflection means impedance increased — typically an open circuit or broken conductor. A negative reflection means a short circuit or low-resistance fault.

Why does my TDR show nothing even though the cable is dead? You likely have a high-resistance fault (above a few hundred ohms), which reflects too little energy to measure. Condition the fault first with a bridge or burnout method.

How important is waveform storage? Critical for professional work. Trace comparison against a baseline is the most reliable way to distinguish new faults from normal cable features.

Need the instrument behind this method?

We build the TDR, surge and pinpointing equipment described in these articles.